| Specification |
Shell Material: Stainless Steel;
Voltage Level: High Voltage;
Installation: Removable;
Structure: Cabinet;
Current: DC;
The Rated Voltage: 12kv;
Rated Frequency: 50Hz;
Power Frequency Withstand Voltage: 42/48kv;
Lightning Shock Withstand Voltage: 75/85kv;
Rated Current: 1250/630A;
Rated Closed Loop Breaking Current: 630A;
Rated Cable Charging Break Current: 10A;
Rated Short Circuit Closing Current: 50-80A;
|
Shell Material: Stainless Steel;
Voltage Level: High Voltage;
Installation: Removable;
Structure: Cabinet;
Current: AC;
Rated Voltagea: 12kv;
Rated Frequency: 50Hz;
Protection Class: IP4X(Cabinet)/IP2X(with Door Open);
Compliance Standards: IEC-298;
Ambient Temperature: -10℃~+40℃;
Altitude: ≤1000m;
Relative Humidity: ≤95% (Daily Avg), ≤90% (Monthly Avg);
Five-Prevention Function: Yes (Prevents Misoperation);
|
Shell Material: Steel Plate;
Voltage Level: High Voltage;
Installation: Fixed;
Structure: Cabinet;
Current: AC;
Altitude: 1000m;
Ambient Air Temperature: 40°C Max, -15°C Min.;
Rated Frequency: 50Hz;
Current Rating: 630A/1250A/1300A;
Rated Peak Withstand Current: 50ka\63ka\80ka;
Rated Voltage: 40.5 Kv;
Main Busbar: 630A/1250A/1300A;
Equipped with a Circuit Breaker: 630A/1250A/1300A;
1min Power Frequency Tolerance: 95/110kv;
Lightning Shock Resistance: 185/215kv;
Auxiliary, Control Loop Tolerance: 2000V/1min;
Rated Short-Time Withstand Current/Rated: 20ka/4s,25ka/4s,31.5ka/4s;
Rated Short-Circuit Interrupting Current: 20ka,25ka,31.5ka;
Rated Short-Circuit Closing Current: 50ka,63ka,80ka;
Rated Voltage of The Control Loop: DC:110V,220V,AC:110V,220V;
|
Shell Material: Stainless Steel;
Voltage Level: High Voltage;
Installation: Removable;
Structure: Cabinet;
Current: AC;
Rated Voltagea: 12kv;
Rated Frequency: 50Hz;
Protection Class: IP4X(Cabinet)/IP2X(with Door Open);
Compliance Standards: IEC-298;
Ambient Temperature: -10℃~+40℃;
Altitude: ≤1000m;
Relative Humidity: ≤95% (Daily Avg), ≤90% (Monthly Avg);
Five-Prevention Function: Yes (Prevents Misoperation);
|
Shell Material: Steel Plate;
Voltage Level: Low Voltage;
Installation: Removable;
Structure: Cabinet;
Current: AC;
The Main Bus Is Rated for Withstand Curr: 100ka;
The Maximum Working Current of The Main: 5000A;
The Main Bus Is Rated for Peak Withstand: 220ka;
Rated Insulation Voltage: 660V;
Rated Operating Voltage: 380V/660V;
Product Model: Mns-0.4;
The Maximum Working Current of The Distr: 1000ka;
Standard: 105ka (Max);
Strengthened: 176ka (Max);
High: 2000;
Wide: 600/800/1000;
Deep: 600/800/1000;
Ingress Protection: Compliant with IEC529, DIN40050 Standards;
|